GE Power Management
ALPS Advanced Line Protection System
2-73
2 CALCULATION OF SETTINGS
2.5 REFERENCE TABLES
2
2.5.5 GENERAL SETTINGS DATA SHEETS
Table 2–14: GENERAL SETTINGS DATA SHEET (Sheet 1 of 2)
NO.
MNEMONIC
DESCRIPTION
RANGE (5A & 1A)
STEP
USER SETTING
CONFIGURE
101
UNITID
Unit ID
0000 to 9999
1
102
SYSFREQ
System Frequency
50 Hz, 60 Hz
N/A
103
PHASROTATE
Phase Rotation
ABC, ACB
N/A
104
TIMESYNCH
Time Synch Source
INTERNAL, IRIG-B
N/A
105
NUM_BKR
Number of Breakers
1, 2
N/A
106
NUM_TC
Number of Trip Circuits
1, 2
N/A
107
NUM_MON
Number of Trip Circuit Monitors
for 1P tripping:
format = abcdef;
for 3P tripping:
format = abcd
a-f = 0 (on) or 1(off)
108
DISPLAYVAL
Value Display Mode
PRI, SEC
N/A
109
LANGUAGE
Language Option
ENGLISH, SPANISH
N/A
110
SYSIN1-4
System Inputs 1 to 4
0000 to 1111 (binary)
0 to 15 (decimal)
1
COMMPORTS
201
COMPORT1
Communications Port #1
Settings
Baud Rate (xx), Parity
(y), Stop Bits (z)
format = xxyz
xx = 03, 12, 24, 48, 96,
19;
y = 0 (none), 1 (odd), 2
(even);
z = 1, 2
202
COMPORT2
Communications Port #2
Settings
Interface (i), Baud Rate
(xx), Parity (y), Stop Bits
(z)
format = ixxyz
i = 0 (RS232), 1
(RS485); xx = 03, 12,
24, 48, 96, 19; y = 0
(none), 1 (odd), 2
(even);
z = 1, 2
203
COMPORT3
Communications Port #3
Settings
Interface (i), Baud Rate
(xx), Parity (y), Stop bits
(z)
format = ixxyz
i = 0 (RS232), 1
(RS485); xx = 03, 12,
24, 48, 96, 19; y = 0
(none), 1 (odd), 2
(even);
z = 1, 2
204
PROTOCOL1
Communications Port #1
Protocol
GE-MODEM, ASCII
N/A
205
PROTOCOL2
Communications Port #2
Protocol
GE-MODEM, ASCII
N/A
206
PROTOCOL3
Communications Port #3
Protocol
GE-MODEM, ASCII
N/A
OSC_GRAPHY
301
NUMFAULTS
Number of Fault Records
2,4,8,12
(std. mem.)
6,12,24,36
(exp mem)
†
N/A
302
PREFAULT
Number of Pre-fault Cycles
1 to 8
1
303
SPLITREC
Splits Fault Record and
captures this percentage at end,
with 1-SPLITREC captured at
beginning
0 to 100%
1
BRKR DUTY
401
EXPONENT
Exponent in
I
x
t
calculation
1.0 to 2.0
0.1
402
MAX_OP
Maximum Number of Breaker
Operations for a Breaker
0 to 9999
1
403
MAX_IXT
Maximum Breaker Duty for a
Breaker
0 to 9999999 A
x
sec.
100
† Applicable to the Single Phase Tripping model only.
‡ Applicable to the Three Phase Tripping model only.
* Contact converter output normally appears as a Logic 1 with normally open contact connected; to invert output to Logic 0, add 1000 to