10-8
ALPS Advanced Line Protection System
GE Power Management
10.3 FILE MENU
10 ALPS TEST PROGRAM
10
10.3 FILE MENU
10.3.1 NEW TEST FILE
The File menu is shown below:
Figure 10–13: FILE MENU
Select New Test File from the File menu. This will create a new test which is indicated by the GE logo being displayed and
the test name “Untitledx” in the title bar. The ‘x’ is a digit corresponding to the number of new documents created.
10.3.2 OPEN TEST FILE
This menu item results in a dialog box supplied by Microsoft. Therefore only the OK button of the dialog box is tested to
make sure the file was properly opened.
Select Open Test File from the File menu. Select a file that is not a test file and not a setting file. A message box is dis-
played that explains the error. Verify that the currently active test has not changed from before the open command.
Edit an existing test file using a text editor. Add a line to the file. Select Open Test File from the File menu. Select the
edited file. A message box is displayed that explains the error. Verify that the currently active test has not changed from
before the open command.
Edit an existing test file using a text editor. Remove a line which contains a user entered value that is not a default value.
Select Open test File from the File menu. Select the edited file. A message box is displayed explaining the error. Verify
that the test file is still loaded and that the missing value has its default value.
Select Open Test File from the File menu. Select a test file containing no errors and click the OK button to open it. Select
a test. Verify that the values in the dialog box are the same as those in the file (see the Save Input Quantities section).
10.3.3 OPEN SETTING FILE
The following is a list of protection setting numbers whose values are used by this test program.
102
Z1PREACH
Z1 Phase Reach
105
Z1GRDREACH
Z1 Ground Reach
108
Z1GROUNDK0
Z1 Ground K0
202
Z2PHREACH
Z2 Phase Reach
203
Z2PCHARANG
Z2 Phase Characteristic Angle
206
Z2GRDREACH
Z2 Ground Reach
207
Z2GCHARANG
Z2 Ground Characteristic Angle
302
Z3PHREACH
Z3 Phase Reach
303
Z3PCHARANG
Z3 Phase Characteristic Angle
305
Z3GRDREACH
Z3 Ground Reach
306
Z3GCHARANG
Z3 Ground Characteristic Angle
402
Z4PHREACH
Z4 Phase Reach
403
Z4PCHARANG
Z4 Phase Characteristic Angle
406
Z4GRDREACH
Z4 Ground Reach
407
Z4GCHARANG
Z4 Ground Characteristic Angle
408
Z4DIRECTN
Z4 Direction