GE Power Management
ALPS Advanced Line Protection System
2-61
2 CALCULATION OF SETTINGS
2.5 REFERENCE TABLES
2
SCADA_DTA
1501
FLTLOCK
Hold Time
0 to 99.9 sec. step 0.1
0 sec.
1502
FLTRESET
Fault Location Reset Time
0 to 999 minutes step 1
0 minutes
OS BLOCKING
1601
MOBZONE
Coordinating Zone
ZONE2, ZONE3, ZONE4
ZONE3
1602
MOBCHARANG
MOB Characteristic Angle
30 to 130 deg. step 1
70 deg.
1603
BLOCKWHAT
Block during OS
BLKALL, BLKDIST, BLKPHAS, BLKNONE
BLKALL
1604
BLOCKZ1
Block all Zone 1 Functions
NO, YES
YES
1605
BLOCKZ2
Block all Zone 2 Functions
NO, YES
YES
1606
BLOCKZ3
Block all Zone 3 Functions
NO, YES
YES
1607
BLOCKZ4
Block all Zone 4 Functions
NO, YES
YES
OS TRIPPING (OUT-OF-STEP TRIPPING MODELS ONLY)
1701
USE_OST
Select OST
NO, YES
NO
1702
NUMBRCHAR
Select Number of Characteristics
2, 3
3
1703
TRIPIN_OUT
Trip Entering or Leaving Inner
IN, OUT
OUT
1704
FWDREACH
OST Forward Reach
0.1 to 75.0 ohms
step 0.1
0.5 to 375.0 ohms
step 0.5
15.0
Ω
at 5A
75.0
Ω
at 1A
1705
REVREACH
OST Reverse Reach
0.1 to 75.0 ohms
step 0.1
0.1 to 375.0 ohms
step 0.5
5.0
Ω
at 5A
25.0
Ω
at 1A
1706
OUTER
Outer Characteristic Angle
40 to 165 deg. step 1
90 deg.
1707
MIDDLE
Middle Characteristic Angle
40 to 165 deg. step 1
105 deg.
1708
INNER
Inner Characteristic Angle
40 to 165 deg. step 1
120 deg.
1709
TLOS1PU
Coordinating Timer 1 Pickup
1 to 100 msec. step 1
40 msec.
1710
TLOS1DO
Coordinating Timer 1 Dropout
1 to 100 msec. step 1
40 msec.
1711
TLOS2PU
Coordinating Timer 2 Pickup
1 to 100 msec. step 1
40 msec.
1712
TLOS3PU
Coordinating Timer 3 Pickup
1 to 100 msec. step 1
40 msec.
1713
TLOS4PU
Coordinating Timer 4 Pickup
1 to 100 msec. step 1
40 msec.
RECLOSER
1801
RECLMODE
Select Reclosing Option
OFF, NONE, INTERNAL, EXTERNAL, BOTH
OFF
1802
^
RECTYPE
Set Reclosing Type
1POLE, 3POLE, 1POLE/3POLE
3POLE
1803
^
NUM1P
Number of Attempts Following 1P
Trip
1 to 4 step 1
1
1804
^
1PDELAY1
1 Pole First Delay
0.1 to 300 sec. step 0.1
0.1 sec.
1805
^
1PDELAY2
1 Pole Second Delay
0.1 to 300 sec. step 0.1
0.1 sec.
1806
^
1PDELAY3
1 Pole Third Delay
0.1 to 300 sec. step 0.1
0.1 sec.
1807
^
1PDELAY4
1 Pole Fourth Delay
0.1 to 300 sec. step 0.1
0.1 sec.
1808
NUM3P
Number of Attempts Following 3P
Trip
1 to 4 step 1
1
1809
3PDELAY1
3 Pole First Delay
0.1 to 300 sec. step 0.1
0.1 sec.
1810
3PDELAY2
3 Pole Second Delay
0.1 to 300 sec. step 0.1
0.1 sec.
1811
3PDELAY3
3 Pole Third Delay
0.1 to 300 sec. step 0.1
0.1 sec.
1812
3PDELAY4
3 Pole Fourth Delay
0.1 to 300 sec. step 0.1
0.1 sec.
1813
RESETTIME
Reset Time
0.1 to 300 sec. step 0.1
1 sec.
1814
DWELLTIME
Contact Dwell Time
0.1 to 2 sec. step 0.1
0.1 sec.
1815
HOLD
Inhibit Hold Select
NO, YES
NO
1816
HOLDTIME
Inhibit Hold Time
1 to 1000 sec. step 1
1 sec.
Table 2–11: PROTECTION SETTINGS GUIDE (Sheet 5 of 7)
NO.
MNEMONIC
DESCRIPTION
RANGE (5A)
RANGE (1A)
DEFAULT
† Setting value QUAD applies to Revision B models only.
‡ Setting applicable to Revision B models only.
^ Setting applicable to Single Phase Tripping models only.