GE Power Management
ALPS Advanced Line Protection System
2-65
2 CALCULATION OF SETTINGS
2.5 REFERENCE TABLES
2
403
MAX_IXT
Maximum Breaker Duty for a
Breaker
0 to 9999999 A
x
sec.
100
0
404
IXTPHASEA
Accumulated Breaker Duty,
Phase A
0 to 9999999 A
x
sec.
100
0
405
IXTPHASEB
Accumulated Breaker Duty,
Phase B
0 to 9999999 A
x
sec.
100
0
406
IXTPHASEC
Accumulated Breaker Duty,
Phase C
0 to 9999999 A
x
sec.
100
0
407
‡
NUM_OP
Present Number of Breaker
Operations
0 to 9999
1
0
407
†
NUM_OP_A
Present Number of Breaker
Operations for Phase A
0 to 9999
1
0
408
†
NUM_OP_B
Present Number of Breaker
Operations for Phase B
0 to 9999
1
0
409
†
NUM_OP_C
Present Number of Breaker
Operations for Phase C
0 to 9999
1
0
INPUTS
501
CC1
Contact Converter 1
0 to 32 *
1
12
502
CC2
Contact Converter 2
0 to 32 *
1
13
503
CC3
Contact Converter 3
0 to 32 *
1
10
504
CC4
Contact Converter 4
0 to 32 *
1
11
505
CC5
Contact Converter 5
0 to 32 *
1
7
†
506
CC6
Contact Converter 6
0 to 32 *
1
507
CC7
Contact Converter 7
0 to 32 *
1
1
†
508
CC8
Contact Converter 8
0 to 32 *
2
†
, 4
‡
509
CC9
†
Contact Converter 9
0 to 32 *
1
3
†
510
CC10
†
Contact Converter 10
0 to 32 *
1
4
†
511
CC11
†
Contact Converter 11
0 to 32 *
1
5
†
512
CC12
†
Contact Converter 12
0 to 32 *
1
6
†
Table 2–12: GENERAL SETTINGS GUIDE (Sheet 2 of 2)
NO.
MNEMONIC
DESCRIPTION
RANGE
(5A & 1A)
STEP
DEFAULT
† Applicable to the Single Phase Tripping model only.
‡ Applicable to the Three Phase Tripping model only.
* Contact converter output normally appears as a Logic 1 with normally open contact connected; to invert output to Logic 0, add 1000 to
the number.