2-70
ALPS Advanced Line Protection System
GE Power Management
2.5 REFERENCE TABLES
2 CALCULATION OF SETTINGS
2
1408
PTRATIO
PT Ratio
1 to 7000 step 1
SCADA_DTA
1501
FLTLOCK
Hold Time
0 to 99.9 sec. step 0.1
1502
FLTRESET
Fault Location Reset Time
0 to 999 minutes step 1
1601
MOBZONE
Coordinating Zone
ZONE2, ZONE3, ZONE4
OS BLOCKING
1602
MOBCHARANG
MOB Characteristic Angle
30 to 130 deg. step 1
1603
BLOCKWHAT
Block during OS
BLKALL, BLKDIST, BLKPHAS, BLKNONE
1604
BLOCKZ1
Block all Zone 1 Functions
NO, YES
1605
BLOCKZ2
Block all Zone 2 Functions
NO, YES
1606
BLOCKZ3
Block all Zone 3 Functions
NO, YES
1607
BLOCKZ4
Block all Zone 4 Functions
NO, YES
OS TRIPPING (OUT-OF-STEP TRIPPING MODELS ONLY)
1701
USE_OST
Select OST
NO, YES
1702
NUMBRCHAR
Select Number of Characteristics
2, 3
1703
TRIPIN_OUT
Trip Entering or Leaving Inner
IN, OUT
1704
FWDREACH
OST Forward Reach
0.1 to 75.0 ohms
step 0.1
0.5 to 375.0 ohms
step 0.5
1705
REVREACH
OST Reverse Reach
0.1 to 75.0 ohms
step 0.1
0.1 to 375.0 ohms
step 0.5
1706
OUTER
Outer Characteristic Angle
40 to 165 deg. step 1
1707
MIDDLE
Middle Characteristic Angle
40 to 165 deg. step 1
1708
INNER
Inner Characteristic Angle
40 to 165 deg. step 1
1709
TLOS1PU
Coordinating Timer 1 Pickup
1 to 100 msec. step 1
1710
TLOS1DO
Coordinating Timer 1 Dropout
1 to 100 msec. step 1
1711
TLOS2PU
Coordinating Timer 2 Pickup
1 to 100 msec. step 1
1712
TLOS3PU
Coordinating Timer 3 Pickup
1 to 100 msec. step 1
1713
TLOS4PU
Coordinating Timer 4 Pickup
1 to 100 msec. step 1
RECLOSER
1801
RECLMODE
Select Reclosing Option
OFF, NONE, INTERNAL, EXTERNAL, BOTH
1802
^
RECTYPE
Set Reclosing Type
1POLE, 3POLE, 1POLE/3POLE
1803
^
NUM1P
Number of Attempts Following 1P
Trip
1 to 4 step 1
1804
^
1PDELAY1
1 Pole First Delay
0.1 to 300 sec. step 0.1
1805
^
1PDELAY2
1 Pole Second Delay
0.1 to 300 sec. step 0.1
1806
^
1PDELAY3
1 Pole Third Delay
0.1 to 300 sec. step 0.1
1807
^
1PDELAY4
1 Pole Fourth Delay
0.1 to 300 sec. step 0.1
1808
NUM3P
Number of Attempts Following 3P
Trip
1 to 4 step 1
1809
3PDELAY1
3 Pole First Delay
0.1 to 300 sec. step 0.1
1810
3PDELAY2
3 Pole Second Delay
0.1 to 300 sec. step 0.1
1811
3PDELAY3
3 Pole Third Delay
0.1 to 300 sec. step 0.1
1812
3PDELAY4
3 Pole Fourth Delay
0.1 to 300 sec. step 0.1
1813
RESETTIME
Reset Time
0.1 to 300 sec. step 0.1
1814
DWELLTIME
Contact Dwell Time
0.1 to 2 sec. step 0.1
Table 2–13: PROTECTION SETTINGS DATA SHEET (Sheet 5 of 7)
NO.
MNEMONIC
DESCRIPTION
RANGE (5A)
RANGE (1A)
USER
SETTING
† Setting value QUAD applies to Revision B models only.
‡ Setting applicable to Revision B models only.
^ Setting applicable to Single Phase Tripping models only.