8.2.11 OSCILLOGRAPHY SNAPSHOT
This command can be used to trigger the immediate collection of oscillography data. Oscillography can be triggered without
at any privilege level. The user will be prompted to start the trigger.
OSC SNAPSHOT
Trigger Osc?
Table 8–2: KEYPAD / DISPLAY INTERFACE ERROR MESSAGES
ERROR MESSAGE
CAUSE OF ERROR
VAL OUT OF RANGE
The setting value is either greater than the upper limit or less than the lower limit.
sett num invalid
The setting number is not valid.
y/n not entered
A YES or NO response key was required, but the [1/Y] or [3/N] key was not pressed.
request invalid
A key was pressed that is not valid for a sequence; for example:
The [ENT] key is pressed to view events.
The _ key is pressed during entry of a settings value.
category invalid
An incorrect category number was entered for an action or information item.
bkr num invalid
A breaker number other than 1 or 2 was entered.
date invalid
The day, month, or year entry is invalid.
time invalid
The hour, minute, or seconds entry is invalid.
fault # invalid
An out of range fault number was entered.
remote link act
The remote communication link is in use for actions or settings; local settings or changes can’t be done.
LUi key error
The LUI received an invalid key code from the keyboard (hardware error).
act invalid now
The current action is invalid because the setting’s CRC code is in error.