GE Power Management
ALPS Advanced Line Protection System
2-43
2 CALCULATION OF SETTINGS
2.3 PROTECTION SETTINGS
2
1807: 1PDELAY4 - Single Pole Fourth Reclose Delay (Single Phase Tripping models only)
1PDELAY4 establishes the delay to be used for the fourth reclose attempt following the initial single-pole trip (this will be a
three-pole reclose). The delay time can be set over a range of 0.1 to 300.0 seconds. Select a setting suitable for the appli-
cation.
1808: NUM3P - Number Of Attempts Following a Three-pole Trip
NUM3P sets the number of reclosure attempts following a three-pole trip. NUM3P can be set as follows:
1.
one reclosing attempt (three-pole)
2.
two reclosing attempts (all three-pole)
3.
three reclosing attempts (all three-pole)
4.
four reclosing attempts (all three-pole)
Select a value suitable for the application.
1809: 3PDELAY1 - Three Pole First Reclose Delay
3PDELAY1 establishes the delay to be used for the first three-pole reclose attempt. The delay time can be set over a range
of 0.1 to 300.0 seconds. Select a setting suitable for the application.
1810: 3PDELAY2 - Three Pole Second Reclose Delay
3PDELAY2 establishes the delay to be used for the second three-pole reclose attempt. The delay time can be set over a
range of 0.1 to 300.0 seconds. Select a setting suitable for the application.
1811: 3PDELAY3 - Three Pole Third Reclose Delay
3PDELAY3 establishes the delay to be used for the third three-pole reclose attempt. The delay time can be set over a
range of 0.1 to 300.0 seconds. Select a setting suitable for the application.
1812: 3PDELAY4 - Three Pole Fourth Reclose Delay
3PDELAY4 establishes the delay to be used for the fourth three-pole reclose attempt. The delay time can be set over a
range of 0.1 to 300.0 seconds. Select a setting suitable for the application.
1813: RESETTIME - Reset Time
RESETTIME is the time after the reclose signal has been produced that the recloser waits before going to the reset posi-
tion. If a trip occurs during RESETTIME, the recloser goes to the next programmed reclose, or to lockout, if the trip
occurred following the last programmed reclose attempt. The reset time delay can be set over a range of 0.1 to 300.0 sec-
onds.
1814: DWELLTIME - Contact Dwell Time
DWELLTIME establishes the time that the closing contacts will stay closed following a reclose output. Select a time suitable
for the application. The dwell time can be set over a range of 0.1 to 2.0 seconds.
1815: HOLD: Inhibit Hold Select
HOLD can be set to YES or NO and determines whether the HOLD feature of the recloser will be employed.
1816 HOLDTIME - Inhibit Hold Time
If HOLD is set to YES, then HOLDTIME establishes the time that the recloser will wait for hold input defined by Protection
Setting 1817: HOLDSENSE to occur before sending the recloser to lockout. HOLDTIME has a setting range of 1 to 1000
seconds.
1817 HOLDSENSE - Contact Input Status
HOLDSENSE can be set to:
CC: contact closed
CO contact open