C-2
ALPS Advanced Line Protection System
GE Power Management
C.2 DEVICE PROFILE
APPENDIX C
C
C.2 DEVICE PROFILE
C.2.1 DNP V3.00 DEVICE PROFILE DOCUMENT
DNP 3.0
DEVICE PROFILE DOCUMENT
Vendor Name: General Electric Power Management Inc.
Device Name: ALPS Advanced Line Protection System
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Device Function:
p
Master
Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is
described in the attached table):
Binary Input (Object 1, Variations 1 and 2)
Binary Output (Object 10, Variation 2)
Binary Counter (Object 20, Variations 5 and 6)
Frozen Counter (Object 21, Variations 5 and 6)
Analog Input (Object 30, Variations 1, 2, 3 and 4)
Analog Input Change (Object 32, Variations 1, 2, 3 and 4)
Analog Output (Object 40, Variations 1 and 2)
Analog Output Block (Object 41, Variation 1)
Warm Restart (Function code 14)
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received: 292
Maximum Application Fragment Size (octets):
Transmitted: 2048
Received: 2048
Maximum Data Link Re-tries:
None
p
Fixed
p
Configurable
Maximum Application Layer Re-tries:
None
p
Configurable
Requires Data Link Layer Confirmation:
Never
p
Always
p
Sometimes
p
Configurable
Requires Application Layer Confirmation:
p
Never
p
Always
p
When reporting Event Data
When sending multi-fragment responses
p
Sometimes
p
Configurable
Timeouts while waiting for:
Data Link Confirm
None
p
Fixed
p
Variable
p
Configurable
Complete Appl. Fragment
None
p
Fixed
p
Variable
p
Configurable
Application Confirm
p
None
Fixed at 5000 ms
p
Variable
p
Configurable
Complete Appl. Response
None
p
Fixed
p
Variable
p
Configurable
Others:
(None)
S
S
S
S
S
S
S
S
S