PDU08C13AU
8-Port Rack-Mount PDU with C13 Outlets - 1U - 16 A
*actual product may vary from photos
Introduction
The PDU08C13AU is a cost-effective power distribution solution
that you can mount in your rack to deliver power to your rack-
mounted equipment. The PDU is constructed from durable steel and
mounts horizontally in your rack, taking up only 1U of space. The
PDU features a dual circuit breaker that is designed to protect your
equipment from power surges, and two reset buttons that you can
use to reset the PDU after a power surge.
Product diagram
C13 outlets
Reset buttons
C20 power port
Mounting
holes
Mounting
holes
Package contents
• 1 x rack-mount PDU
• 1 x 10 ft. (3 m) C19 to AS3112 power cord
• 4 x screws
• 4 x cage nuts
• 1 x instruction manual
Requirements
• Power source
• 1U of space in a server rack
Requirements are subject to change. For the latest requirements,
.
Install the rack-mount PDU
The rack-mount PDU takes up 1U of space.
1. Line up the
Mounting holes
on the rack-mount PDU with the
mounting holes on your server rack.
2. Use the provided screws and cage nuts or the mounting hardware
that came with your rack to attach the rack-mount PDU to your
server rack.
3. Connect the power cord to the
C20 power port
on the rack-
mount PDU and a power source. Make sure that you connect the
power cord directly to the power source and not another PDU.
4. Connect the devices in your server rack to the
C13 outlets
on the
rack-mount PDU.
Caution!
The combined power draw of all of the devices attached to
the rack-mount PDU shouldn’t exceed 16 A, otherwise you will trip
the built-in circuit breaker.
Troubleshooting
What do I do if I trip the circuit breaker?
If you trip the circuit breaker, complete the following:
1. Make sure that the combined power draw of all of the devices
attached to the rack-mount PDU doesn’t exceed 16 A.
2. Press one of the
Reset buttons
on the rack-mount PDU.
Specifications
Input
C20
Output
C13 (x8)
Voltage
100 to 240 V ac
Maximum current
16 A
Number of fuses
2