background image

Model

Available Input

 Voltages

Outlets

Available Input

 Cord

Amperage

Dimensions

(L x W x D)

© Server Technology, Inc. 01/26/2007 version. Information in this document is subject to change without notice. Sentry is a trademark of Server Technology, Inc. 
Protected by one or more of the following patents: Patent # 7,043,543. Patent Pending. Printed in US.

Sentry :

 Solutions for the Data Center Equipment Cabinet

Key Features

Sentry :

 CDU Technical Specifications

Sentry Switched CDU

CW-16V (20-Amp)

High-Density Power Distribution

The Switched CDU’s combine remote configuration and management 
with power distribution and power and environmental monitoring. 
Reboot a single or dual-power server with one command. Receive 
SNMP-based alerts and email alerts when power or environmental 
conditions exceed thresholds. Assign users specific access rights to 
designated outlets or groups. 

Only the Switched CDU products provide the flexibility needed for all 
data centers and remote sites, including power requirements for 
high-amp, high voltage; UL 60950-1 (branch circuit protection not 
required for 20A rated devices); SSL & SSH security; and SNMP-based 
input current monitoring.

The Switched CDU also supports  Enterprise View PDU Manager. 
This gives the engineer the ability to manage  a large installation of 
Networked CDUs from one location, view and access up to 1,000 
Switched CDUs from a 

single web interface. 

> Remote Power Management:

 

Power cycle individual power 

outlets, or groups of power 

outlets, to remotely reboot 

servers and network devices, 

anywhere in the world.  Or, 

power-off unused power 

receptacles

> High Power Distribution

: 120V, 

208V, or 230V power; 20-Amp 

power input feed option

> High Density: 

 Single power 

input feed; 16 outlets per 

enclosure

> IP Access & Security: 

 Web 

interface, SSL, SSH, Telnet, SNMP, 
FTP, SNTP, Syslog, LDAP, LDAPS, 
TACACS

 

and RS-232 access

> Add an Expansion Module: 

 

Daisy chain the Switched CDU 

Expansion Module (CW/CX) for 

power management of separate 

power circuits from a single IP 

address  

> Environmental Monitoring: 

 

Each Switched CDU supports two 

temperature & humidity probes 

and reports conditions thru the 

Web interface

> Enterprise View: 

 View and 

access up to 1,000 Switched 

CDUs from one Web interface**

> SNMP Traps: 

Provide automated 

alerts for power and 

environmental conditions

> Input Current Monitor:

 

Precisely measure the aggregate 

current draw (in amps) on each 

power circuit.  On-site 

verification of the input current 

with the LED digital display.  

Remote verification via browser 

or serial screen.

Power-up Sequencing:

 Prevent 

an in-rush power overload

 

Input Current Monitoring

 

The CDU’s exclusive True RMS current monitoring is critical 
to preventing overloads in high-density computing  
environments.  LED digital displays on the CDU enclosure 
report the input current of each phase or branch circuit.

              

Temperature and Humidity 

   

 

 

The Switched CDU supports two external probes. Each of 
these probes measure both temperature and humidity.  
Receive SNMP-based alert notifications when conditions 
exceed defined thresholds.

              

Additional Benefits:

CW-16V1-C20MX

CW-16V2-C20MX

100-120V

50/60Hz

208-240V

50/60Hz

20A

20A

IEC 60320/C20

Power Inlet

IEC 60320/C20

Power Inlet

(16) NEMA 5-20R

(16) IEC 60320/C13

39.5” x 1.75” x 2.25”

39.5” x 1.75” x 2.25”

Additional Features and Specifications

Agency Approvals

> US & Canada (cTUVus mark) to UL 60950-1:2003 and               

   CAN/CSA 22.2 No. 60950-1-03 

        

> European Union (TUVGS mark) to EN 60950-1:2001  

> FCC Class A, Part 15 

    

> CE

> EMC - EN 55022 Class A, EN 55024

Communications and Security

> 10/100 BaseT Ethernet 

        

> HTTP/HTTPS  

        

> SSLv3/TLSv1  

       

> SNMPv2   

 

        

> SSHv2

> Telnet

> LDAPv3 and LDAPS 

> RS-232 (Serial)

Accessories

> Optional Temperature & Humidity Probe

 

EMTH-1-1 Temperature & Humidity Probe, 10’

 

Power Cord Options

> PTCORD-1       IEC 60320/C19 - NEMA L6-20P , 10’

> PTCORD-2       IEC 60320/C19 - Schuko 10’ 

> PTCORD-3       IEC 60320/C19 - IEC 60309 (BS4343, CEE17) 

                            16/20A Blue (UK Commando) 10’

> PTCORD-4       IEC 60320/C19 - BS1363 13A (UK) 10’

> PTCORD-5       IEC 60320/C19 - 5-15P (15A Straight-Blade) 10’

> PTCORD-6       IEC 60320/C19 - 5-20P (20A Straight-Blade) 10’

> PTCORD-7       IEC 60320/C19 - L5-20P (20A Twist-Lock) 10’

> PT-ADP-C19    Cable mount IEC 60320/C19 Connector

**Enterprise View sold separtely

Expansion Module 
Model Numbers

> CX-16V1-C20MX
> CX-16V2-C20MX
> CX-16VE-C20MX

 CW-16VE-C20MX

230V

50/60Hz

16A

IEC 60320/C20

Power Inlet

(16) IEC 60320/C13

39.5” x 1.75” x 2.25”

NORTH AMERICA / ASIA

Server Technology, Inc.

1040 Sandhill Drive

Reno, NV 89521

United States

 1.775.284.2000  Tel

1.775.284.2065 Fax

[email protected]

www.servertech.com

www.servertechblog.com

EMEA

Server Technology Intl

Sienna Court

The Broadway

Maidenhead

Berkshire

SL6 1NJ

United Kingdom

+44 (0) 1628 509053  Tel

+44 (0) 1628 509100 Fax

[email protected]

Branch Circuit Protection 

(not required)

> Compliant to UL 60950-1