Installation manual.
CNC 8060
CNC 8065
3.
INTRODUCTION TO
THE PLC.
Ope
ra
ti
on
of a
timer.
·330·
(R
EF
: 1709)
3.5.1
Monostable mode. TG1 input.
In this operating mode, the status of the timer is maintained high (T=1) from when the TG1
input is activated until the indicated time period (constant) has elapsed.
With TEN=1 and TRS=0, the timer is activated with an up-flank at trigger input TG1. At that
moment, the timer status output (T) changes states (T=1) and the timing starts from ·0·.
Once the time period indicated by the time constant has elapsed, the timing is over. The
status output (T) changes (T=0) and the elapsed time t is maintained.
Any changes at the TG1 input (up or down-flank) while timing, has no effect.
Once the timing is over, an up-flank at trigger input TG1 is required to reactivate the timer.
Operation of the TRS input in this mode.
If an up-flank occurs at the TRS input while timing or after it, the PLC resets the timer setting
its status output low (T=0) and resetting its timing (t=0).
Since the timer is reset, its trigger input must be activated again to turn it back on.
Summary of Contents for CNC 8060
Page 1: ...Ref 1709 8060 8065 CNC Installation manual...
Page 10: ...BLANK PAGE 10...
Page 14: ...BLANK PAGE 14...
Page 20: ...BLANK PAGE 20...
Page 32: ...BLANK PAGE 32...
Page 36: ...BLANK PAGE 36...
Page 38: ...BLANK PAGE 38...
Page 40: ...BLANK PAGE 40...
Page 41: ...PART 1 INSTALLATION MANUAL...
Page 42: ...BLANK PAGE 42...
Page 532: ...Installation manual CNC 8060 CNC 8065 9 CNC VARIABLES 532 REF 1709...
Page 533: ...PART 2 CONCEPTS...
Page 534: ...BLANK PAGE 534...
Page 548: ...Installation manual CNC 8060 CNC 8065 10 GENERAL SETUP Configuration examples 548 REF 1709...
Page 644: ...Installation manual CNC 8060 CNC 8065 14 SUBROUTINES Assistance for subroutines 644 REF 1709...
Page 668: ...Installation manual CNC 8060 CNC 8065 15 HARDWARE Configure the PT100 inputs 668 REF 1709...
Page 697: ...Installation manual CNC 8060 CNC 8065 697 User notes REF 1709...