RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
283
EN
HANCED
TEC
HNOLOGY
13.28. Recloser Trip and Close Circuits
Figure 13-28. Recloser Trip and Close Circuits
CC
Close Coil
TC
Trip Coil
MC
Magnetic Contactor
C
Capacitor
IGBT
Insulated Gate Bipolar Transistor
F
Fuse
UPS
Uninterruptible Power Supply
y
Recloser Trip and Close Power is charged from C1, C2, C3 in UPS module.
y
C1 is used for Trip power, C2, C3 are used for Close power.
y
Trip(Close) runs when IGBT is “ON”. MC runs and the charged Capacitor transfer the Power
to TC(CC), eventually Recloser runs.
y
F1, F2 are Fuses to protect IGBT from MC damage. These are on Analog Board.