RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
88
EN
HANCED
TEC
HNOLOGY
6.4. System Power
6.4.1. Description
Menu to set Frequency of Protected Line and installed Phase rotation
6.4.2. Setting
PRIMARY SETTING / SYSTEM SETUP / SYSTEM POWER / Frequency
Range
50, 60
㎐
Default
50
Step
~
Select the nominal power system frequency. This value is used as a
default to set the optimal digital sampling rate.
PRIMARY SETTING / SYSTEM SETUP / SYSTEM POWER / Phase Rotation
Range
ABC, ACB
Default
ABC
Step
~
Select the phase rotation of the power system.
PRIMARY SETTING / SYSTEM SETUP / SYSTEM POWER / Install Direction
Range
NOR(NORMAL), REV(REVERSE)
Default
NOR
Step
~
Select the install direction of Recolser.
During operating after setup, change only this setting to convert a load
side to a source side or reversely.
NOTE :
When the voltage sensor to the load side is installed to
only one phase or none of the phase, the following functions
performed by the voltage measurement are operated incorrectly if
this setting is changed.
y
Directional Control
y
Loss of Phase
y
Synchronism Check
y
Voltage Unbalance Detection
y
Live Load Blocking
y
Loop Control
[SYSTEM POWER]
Frequency: 50
>
Phase Rotation: ABC
>Install Dir’: NOR
[SYSTEM POWER]
Frequency: 50
>Phase Rotation: ABC
>
Install Dir’: NOR
[SYSTEM POWER]
>Frequency: 50
Phase Rotation: ABC
>
Install Dir’: NOR