RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
220
EN
HANCED
TEC
HNOLOGY
8.7. Gas Low Lock - Option
PRIMARY SETTING / MONITORING / GAS LOW LOCK / Function
Range
DISABLE,ENABLE
Default
DISABLE
Step
~
If function = ENABLE,
EVRC2A can’t be opened or closed on the
gas pressure low status (below 0.1bar).
If function = DISABLE,
EVRC2A can be opened or closed even if it
is on the gas pressure low status.
NOTE :
This function is applies only to Gas Type Recloser.
8.8. EXT’ Trip & Lock - Option
This function can make EVRC2A opened and then close lock when the corresponding signal sent
from SCADA is received. And EVRC2A can be reset from close lock status by “FI Reset”
command.
PRIMARY SETTING / MONITORING / EXT’ Trip & Lock / Function
Range
DISABLE,ENABLE
Default
DISABLE
Step
~
If function
=
ENABLE,
EVRC2A will be open and then close locked
when the signal from SCADA is received.
If function = DISABLE,
the function is not activated even if the signal
is received.
PRIMARY SETTING / MONITORING / EXT’ Trip & Lock / USE Inputport
Range
1~8
Default
1
Step
1
Set the port to receive the signal from SCADA.
As example, if “1” is set, this function is activated or not by the signal
value on IN01 port.
[EXT’ Trip & Lock]
>
Function: DISABLE
>USE Inputport: 1
>
Reset Method: LOCAL
[EXT’ Trip & Lock]
>Function: DISABLE
>
USE Inputport: 1
>
Reset Method: LOCAL
[GAS LOW LOCK]
>Function: DISABLE