13.15. Current and Voltage Inputs Phase Rotation
Figure 13-14. Phase Rotation
y
For Metering accuracy, phase rotations of User system and Recloser should be the same.
y
“Figure 13-14. Phase Rotation”
shows the same phase rotation between User System and
Recloser.
y
If the phase rotation is not the same in User system and Recloser, correct CT and VD(CVD
or RVD) wiring in side panel to be matched.
y
EVR Recloser phase A is the Bushing the nearest from Trip lever on the side.