RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
10
EN
HANCED
TEC
HNOLOGY
Table 2-1. Metering Accuracy(2/2)
Measurements
Parameters
Unit
Accuracy
Range
FREQUENCY
A-N (A-B) Source Voltage
R-N (R-S) Load Voltage
㎐
±
0.02
40.00~70.00
HARMONICS
1
st
~7
th
Harmonic of Current
1
st
~7
th
Harmonic of Voltage
THD of Current
THD of Voltage
–
±
1%
±
1%
±
3%
±
3%
0% to 100%
0% to 100%
0% to 100%
0% to 100%
UNBALANCE
Voltage unbalance(V2/V1) in source side
Voltage unbalance(V2/V1) in load side
Current unbalance(I2/I1)
%
±
2%
±
2%
±
2%
0% to 999%
0% to 999%
0% to 999%
If the VT connection type is set to delta, all single phase voltage quantities are displayed as zero.