RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
168
EN
HANCED
TEC
HNOLOGY
Figure 7-10. Phasor Diagram for I
2
Directional Polarization
The negative sequence directional controls in the following four settings should be enabled.
PRIMARY SETTING / PROTECTION / DIRECTION / NEQ DIRECTION / Type
Range
OFF, FOR, REV
Default
OFF
Step
~
OFF :
None direction
FOR :
Forward direction
REV :
Reverse direction
PRIMARY SETTING / PROTECTION / DIRECTION / NEQ DIRECTION / M.T.A
Range
0 ~ 359 degree
Default
135
Step
1 degree
Enter the maximum torque angle. The maximum torque angle setting
determines the directional operating current for the polarizing voltage.
M
ax
imum
Tor
qu
e
Li
ne
-V
2
Ze
ro
T
orqu
e Li
ne
Fo
rw
ar
d
Re
ve
rs
e
I
2
Maximum Torque Angle :
set 135 degree
V
2
Polarizing Referance
Voltage:
Fault Current
[NEQ DIRECTION]
Type: OFF
>M.T.A: 135
M.P.V: 0.20
[NEQ DIRECTION]
>Type: OFF
M.T.A: 135
M.P.V: 0.20