RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
273
EN
HANCED
TEC
HNOLOGY
13.16. Control Cable Receptacle Pin Descriptions
Table 13-2. Control Cable Receptacle Pin Descriptions
Pin
Function
Pin
Function
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
T
U
V
W
X
Z
C.T Phase C
C.T Phase B
C.T Phase A
C.T Common(G)
VD Source Phase C
VD Source Phase B
VD Source Phase A
VD Load side Phase T
VD Load side Phase S
VD Load side Phase R
Pressure Sensor Output(controller input)
not connected
Pressure Sensor Power AGND
Pressure Sensor Power 12Vdc
Cable shield and Ground
not connected
Recloser Status 69b(locked a connect)
Recloser Status Common(24Vdc)
Recloser Status 52b(Monitored Trip)
Recloser Status 52a(Monitored Close)
not connected
not connected
a
b
c
d
e
f
g
h
j
k
m
n
p
r
s
52 common(Auxiliary)
52b(Auxiliary)
52a(Auxiliary)
Close and Trip Coil Common
Close and Trip Coil Common
Close and Trip Coil Common
Close Coil
Close Coil
Close Coil
not connected
Trip Coil
not connected
Trip Coil
Trip Coil
not connected
y
Control EVRC2A Receptacle : MS3102 28-21S(Female)
y
Recloser Receptacle : MS3102 28-21P(Male)
y
Control Cable : Shield Cable 8meter(31.5”)
y
Cable Shielding layer is connected to Pin “R”