RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
56
EN
HANCED
TEC
HNOLOGY
COMMUNICATION/ PROTOCOL SETUP/ IEC870-5-101/ Clock Sync’ Evt*
Range
NO, YES
Default
YES
Step
~
Select whether to generate spontaneous clock synchronization events
NOTE :
The above set values marked with * are indicated from Ver 7.06 of EVRC2A_NT.
5.2.2.4. MODBUS Protocol - Option
EVRC2A can be programmed for communication using the MODBUS through communication
port2, port3 or port4. For details, refer to
“MODBUS Protocol Technical Manual”
Move to
“PRIMARY, ALTERNATE or EDITBANK SETTING
/
RELAY SETUP /
COMMUNICATION / PROTOCOL SETUP / MODBUS”
to select setting for MODBUS
Protocol.
COMMUNICATION/ PROTOCOL SETUP/ MODBUS/ Function
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Set whether to use MODBUS communication or not.
COMMUNICATION/ PROTOCOL SETUP/ MODBUS/ Use Port
Range
P2-232, P3-232, P3-485, P4-TCP
Default
P4-TCP
Step
~
Select MODBUS communication port.
COMMUNICATION/ PROTOCOL SETUP/ MODBUS/ Slave Address
Range
1 ~ 254
Default
1
Step
1
Enter the Modbus address.
[MODBUS]
>
Function: DISABLE
>
Use Port:
P3-485
>Slave Address: 1
[MODBUS]
>
Function: DISABLE
>Use Port:
P3-485
>
Slave Address: 1
[MODBUS]
>Function: DISABLE
Use Port:
P3-485
>
Slave Addr: 1
[IEC60870-5-101]
>
CMD Termination:YES
>
CSE Termination:YES
>Clock Sync’ Evt:YES