RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
98
EN
HANCED
TEC
HNOLOGY
6.8.1. Setting
PRIMARY SETTING / SYSTEM SETUP / LOOP CONTROL / Type Select
Range
NONE, SEC, MID, TIE
Default
NONE
Step
~
Select the Recloser Type and add Loop Control function.
After selecting, press Program 1 Key to enable Loop Control.
NONE :
Loop control is not in use.
SEC :
SECtionalizing Recloser
MID :
MIDpoint Recloser
TIE :
TIEpoint Recloser
PRIMARY SETTING / SYSTEM SETUP / LOOP CONTROL / VRS to S/M
Range
VS, VL
Default
VS
Step
~
Voltage Response Side to SEC&MID :
The setting values are used
in SEC, MID.
Recloser operates upon selected side of voltage sensing.
Select the Voltage response side when Recloser type is SEC & MID
VS :
Recloser’s Source Side(A,B,C phase) Voltage
VL :
Recloser’s Load Side(R,S,T phase) Voltage
Standard Model, EVRC2A uses VD(Voltage divider, CVD or RVD) to
measure the voltage. It measures only A, B, C, R phases, phase S and T
are not measured.
PRIMARY SETTING / SYSTEM SETUP / LOOP CONTROL / VRS to Tie
Range
VS, VL, VS&VL
Default
VS
Step
~
Voltage Response Side to Tie :
The setting value is used in TIE.
TIE operates upon selected side of voltage sensing.
VS :
Recloser’s Source Side(A,B,C phase) Voltage
VL :
Recloser’s Load Side(R,S,T phase) Voltage
VS&VL :
Loop control operates one of either Source side or load side
voltage becomes dead line voltage.
[LOOP CONTROL]
>
Type Select: NONE
>
VRS - S/M: VS
>VRS - Tie: VS
[LOOP CONTROL]
>
Type Select: NONE
>VRS - S/M: VS
>
VRS - Tie: VS
[LOOP CONTROL]
>Type Select: NONE
>
VRS - S/M: VS
>
VRS - Tie: VS