RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
269
EN
HANCED
TEC
HNOLOGY
13.12. Current Inputs Wiring Diagram
Current IG is connected with Side Panel
IG(A07,A08) in Earthing System.
SEF(A09,A10) should be connected, so
called “JUMPER”
IG Input Current Range
y
0.5A Nominal
y
2A continuous
y
25A 1 second
y
Burden : 0.19VA(0.5A)
Current IG should be connected with
SEF(A09,A10) of Side Panel in.
Non Earthing System.
IG(A07,A08) should be connected to each
other.
SEF Input Current Range
y
0.05A Nominal
y
0.16A Continuous
y
0.6A 1 second
y
Burden : 0.0375VA(0.05A)
Figure 13-11. Current Inputs Wiring Diagram
Recloser Phase should match with User system. Refer to
“Figure 13-14. Phase Rotation”
CT Phase rotation must be arranged comparing with Voltage Inputs Phase rotation.