RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
50
EN
HANCED
TEC
HNOLOGY
COMMUNICATION/ PROTOCOL SETUP/ IEC60870-5-101/ ASDU Addr
Range
0~65535
Default
1
Step
1
Select the Application Service Data Unit Address.
COMMUNICATION/ PROTOCOL SETUP/ IEC60870-5-101/ Cyclic Period
Range
1~60000 sec
Default
60
Step
1 sec
Select the Cyclic Period.
It is to set interval time between Point set for Cyclic.
COMMUNICATION/ PROTOCOL SETUP/ IEC60870-5-101/ Event Period
Range
0~255 sec
Default
15
Step
1sec
Select the delay time before events are sent. Single event or several
events occur and then if new event is not generated during the delay
time, the event(s) already generated is(are) sent to a Master.
COMMUNICATION/ PROTOCOL SETUP/ IEC60870-5-101/ Retries
Range
0 ~ 255
Default
0
Step
1
Set the Data retires number.
COMMUNICATION/ PROTOCOL SETUP/ IEC60870-5-101/ Conf. Timeout
Range
1 ~ 255 sec
Default
15
Step
1 sec
Set the wait time till receive the Data Confirm (ACK) of master after
transferring the Data. If there isn’t the Confirm during this setting time
and Data retries is available, EVRC2A transfers the Data again.
COMMUNICATION/ PROTOCOL SETUP/ IEC60870-5-101/ Max Poll Tim
Range
1 ~ 255 sec
Default
60
Step
1 sec
Set the Data Polling period time.
[IEC60870-5-101]
>
Retries:
0
>
Conf.Timeout: 10
>Max Poll Time:
10
[IEC60870-5-101]
>
Retries:
0
>Conf.Timeout: 10
>
Max Poll Time:
10
[IEC60870-5-101]
>Retries:
0
Conf.Timeout: 10
>
Max Poll Time:
10
[IEC60870-5-101]
>
ASDU Addr: 1
>
Cyclic Period: 60
>Event Period: 15
[IEC60870-5-101]
>
ASDU Addr: 1
>Cyclic Period: 60
>
Event Period: 15
[IEC60870-5-101]
>ASDU Addr: 1
>
Cyclic Period: 60
>
Event Period: 15