RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
127
EN
HANCED
TEC
HNOLOGY
7.1.2. Reset
If the faulted current is cleared before the lockout condition, the reclosing sequence
automatically reset after passing the reset time interval.
If the fault condition occurs again during the reset time, the recloser will operate lockout after the
completion of the remaining sequence.
The following block diagram shows the reset sequence operation after the 3rd reclosing as the
fault current is cleared.
(1) 1st Trip - 1st TCC
(2) 1st Reclose Interval Time
(3) 2nd Trip - 2nd TCC
(4) 2nd Reclose Interval Time
(5) 3rd Trip - 3rd TCC
Figure 7-3. Reset Sequence operation after the 3rd reclosing as the fault current is cleared
(1)
(2)
(3)
(4)
(5)
NOMAL
CURRENT
PICKUP
CURRENT
FAULT
CURRENT
AMP
TIME
* RESET *
AUTO RESET
TIME