RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
99
EN
HANCED
TEC
HNOLOGY
PRIMARY SETTING / SYSTEM SETUP / LOOP CONTROL / VS wire
Range
3PN, 3PP, 1PN(A), 1PN(B), 1PN(C), 1PP(AB), 1PP(BC), 1PP(CA)
Default
3PN
Step
~
Line VS Wire :
Select Recloser’s Source side(A,B,C phase) voltage
sensor(VD or VT) connection type.
Selected phase is used to figure dead/live line voltage.
VD type Control measures A, B, C phase voltage.
3PN :
3 Phase-Neutral
3PP :
3 Phase-Phase
1PN(A) :
Phase A-Neutral
1PN(B) :
Phase B-Neutral
1PN(C) :
Phase C-Neutral
1PP(AB) :
Phase A-Phase B
1PP(BC) :
Phase B-Phase C
1PP(CA) :
Phase C-Phase A
PRIMARY SETTING / SYSTEM SETUP / LOOP CONTROL / VL wire
Range
3PN, 3PP, 1PN(A), 1PN(B), 1PN(C), 1PP(AB), 1PP(BC), 1PP(CA)
Default
3PN
Step
~
Line VL Wire :
Select Recloser Load side(R,S,T phase) voltage
sensor(VD or VT) connection type.
Selected phase is used to figure dead/live line voltage.
Select 1PN(A) to measure R phase voltage for VD(CVD or RVD) type
Control S,T phase are not measured.
3PN :
3 Phase-Neutral
3PP :
3 Phase-Phase
1PN(A) :
Phase A-Neutral
1PN(B) :
Phase B-Neutral
1PN(C) :
Phase C-Neutral
1PP(AB) :
Phase A-Phase B
1PP(BC) :
Phase B-Phase C
1PP(CA) :
Phase C-Phase A
[LOOP CONTROL]
>
VS Wire: 3PN
>VL Wire: 1PN(A)
>
Cng Alt-Mid : OFF
[LOOP CONTROL]
>VS Wire: 3PN
>
VL Wire: 1PN(A)
>
Cng Alt-Mid : OFF