RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
133
EN
HANCED
TEC
HNOLOGY
Ground Pickup Current Setup
The following setting is used to program the phase pickup current.
PRIMARY SETTING / PROTECTION / PICKUP CURRENT / Ground
Range
OFF, 10 ~ 1600A
Default
250
Step
1A
Set the pickup current of Ground Time Overcurrent elements.
Ground Fast Time Overcurrent Setup
The following setting is used to program the ground fast time overcurrent element.
PRIMARY SETTING / PROTECTION / GROUND FAST / Function
Range
TRIP, TR&AR
Default
TRIP
Step
~
If function = Trip,
the feature is operational. When the feature asserts
a TRIP condition, which will operate the Trip.
If function = Trip & AR,
the feature is operational. When the feature
asserts a TRIP&AR condition, it trips and alarms.
PRIMARY SETTING / PROTECTION / GROUND FAST / Relays(0-8)
Range
OFF, 0 ~ 8
Default
OFF
Step
1
Selects the relays required to operate when the feature generates a Trip.
PRIMARY SETTING / PROTECTION / GROUND FAST / Curve
Range
ANSI-MI, ANSI-NI, … , KG(165)
Default
ANSI-STI
Step
~
Select the desired curve type :
ANSI :
Moderately, Normally, Very, Extremely, Short Inverse,
Definite Time(1s ,10s)
IEC :
Standard, Very, Extremely, Long, Short Inverse
ESB :
Normally, Very, Long Very Inverse
User programmable curves :
U1,U2,U3,U4
McGraw-Edison :
Non Standard Curves 37
[GROUND FAST]
Function: TRIP
Relays(0-8): OFF
>Curve: ANSI-STI
[GROUND FAST]
Function: TRIP
>Relays(0-8): OFF
Curve: ANSI-STI
[GROUND FAST]
>Function: TRIP
Relays(0-8): OFF
Curve: ANSI-STI
[PICKUP CURRENT(A)]
>
Phase: 500
>Ground: 250
S.E.F: OFF