RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
117
EN
HANCED
TEC
HNOLOGY
SYSTEM SETUP / POWER QUALITY / SAG Duration (Option)
Range
1~60 cycle
Default
5
Step
1
Set a detect time for voltage sag(voltage low).
SYSTEM SETUP / POWER QUALITY / SWL Func (Option)
Range
Disable, Enable
Default
Disable
Step
~
It is to set event recording of swell enable or disable.
SYSTEM SETUP / POWER QUALITY / SWL Pickup (Option)
Range
1.05 ~ 1.25
×
VT(secondary nominal voltage)
Default
1.20
Step
0.01
Set a detect level of voltage swell(high voltage) for Power Quality.
Detect level is set by multiplying a set value in here to source side rated
voltage.
SYSTEM SETUP / POWER QUALITY / SWL Duration (Option)
Range
1~60 cycle
Default
5
Step
1
Set a detect time for voltage swell(voltage high).
SYSTEM SETUP / POWER QUALITY / UBI Func (Option)
Range
Disable, Enable
Default
Disable
Step
~
It is to set event recording of current unbalance enable or disable.
NOTE :
This setting is supported from version 6.12 of EVRC2A-
N6,NT.
>
[POWER QUALITY]
>UBI Func: Disable
>
UBI Pickup: 30
>
UBI Duration: 4.0
>
[POWER QUALITY]
>
SWL Func: Disable
>
SWL Pickup: 1.20
>SWL Duration: 20
>
[POWER QUALITY]
>
SWL Func: Disable
>SWL Pickup: 1.20
>
SWL Duration: 20
>
[POWER QUALITY]
>
SAG Pickup: 0.80
>
SAG Duration: 5
>SWL Func: Disable
>
[POWER QUALITY]
>
SAG Func: Disable
>
SAG Pickup: 0.80
>SAG Duration: 5