RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
265
EN
HANCED
TEC
HNOLOGY
13.8. Terminal Block and Fuses
Figure 13-7. Terminal Block and Fuses
y
Caution for an electric shock due to AC Power loaded in Terminal block.
y
Standard AC Power is 220Vac(Optional AC Power is 110Vac).
y
AC Power input terminal 1, 2 are connected from Receptacle to Terminal block. Terminal 3
is the ground.
y
Terminal 4, 5 are for connecting additional AC Power. Terminal 4 is connected with TF3 for
protection, terminal 5 is in series with AC Power
y
On TF3 Fuse, AC Power Outlet is connected with 40W Heater. Reference for branching.
y
In AC line connection, blue wired line is for Neutral, white wired line is for Phase wire,
green wired line is for the ground.
y
Terminal 6, 7, 8 are spare for Recloser 52 contact.
y
Terminal 9, 10 are for User Available Terminal block. In need of more terminals, use User
Available Space.
52 Contact Auxiliary Specs
Rating (Resistive load) : 30Vdc 5A / 125Vdc 0.6A / 250Vdc 0.3A