RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
250
EN
HANCED
TEC
HNOLOGY
12.4. Diagnostic Event Recorder
Record diagnostic events up to 512 lists when trigger source asserted and deasserted.
MAIN MENU / EVENT RECORDER / DIAGNOSTIC
Confirm in
”MAIN MENU / EVENT RECORDER / DIAGNOSTIC”
12.4.1. Trigger Source
y
SYSTEM POWER : AC, Battery,
±
12V, +5V
y
A/D Conversion : A/D Fail, Reference Voltage1, Reference Voltage 2
y
POWER DOWN MODE
y
GAS STATUS etc
※
. NOTE )
According to a recloser type, there may be no diagnosis of gas pressure status.
y
NOTE :
For more details about Trigger Source, refer to
“Appendix C. EVENT TEXT &
DESCRIPTION”
.
12.4.2. Trigger Time
Monitors status of Trigger source in every 1/4 cycle
12.4.3. Trigger type
Stores type of Trigger source : Pickup(assert) or Dropout(deassert)
12.4.4. Storage Capacity
Stores last 512 events.
12.4.5. Related Setting Menu
System automatically maintains Diagnostic event recorder. User can clear only stored events.
1)
Stored Value Clear
Select
“4.DIAGNOSTIC”
in
“PRIMARY SETTING / RELAY SETUP / CLEAR SAVED
DATA”
to clear.
[NO-001] GAS HIGH
STATUS : LO/DEASSERT
DATE : 10/01/22
TIME : 19:51:58:387
Summary of Contents for EVRC2A-N6-NT