7.6. Phase High Current Trip (50P-1)
The EVRC2A has a phase high current trip element. The phase high current trip element in the
EVRC2A, is set based on CT secondary current as connected to the current inputs. The phase
high current trip element provides a definite time delay versus current.
The operating time of phase high current trip element should be set for equal to or faster than the
phase time overcurrent elements. The phase high current trip element is enabled in the Primary,
Alternate settings and
[PROTECTION ENABLED]
on user interface panel.
Phase high current trip is not affected by the cold load pickup scheme.
The phase high current trip element in the following five settings should be enabled for phase
high current trip.
PRIMARY SETTING / PROTECTION / H/C TRIP-PHA / Function
Range
OFF, TRIP, TR&AR
Default
OFF
Step
~
If function = OFF,
the feature is not operational.
If function = Trip,
the feature is operational. When the feature asserts
a TRIP condition, Trip operates.
If function = Trip & AR,
the feature is operational. When the feature
asserts a TRIP & AR condition, it trips and alarms.
PRIMARY SETTING / PROTECTION / H/C TRIP-PHA / Relays(0-8)
Range
OFF, 0 ~ 8
Default
OFF
Step
1
Selects the required relays to operate when the feature generates a Trip.
PRIMARY SETTING / PROTECTION / H/C TRIP-PHA / Pickup(A)
Range
10 ~ 20000 A
Default
4000
Step
1A
Set the pickup current of Phase High Current Trip Element.
This value is the minimum operating current of Phase High Current
Trip Element.
[ H/C TRIP-PHA ]
Function: OFF
Relays(0-8): OFF
>Pickup(A): 4000
[ H/C TRIP-PHA ]
Function: OFF
>Relays(0-8): OFF
Pickup(A): 4000
[ H/C TRIP-PHA ]
>Function: OFF
Relays(0-8): OFF
Pickup(A): 4000