RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
53
EN
HANCED
TEC
HNOLOGY
COMMUNICATION/ PROTOCOL SETUP/ IEC870-5-101/ CSE Termination*
Range
NO, YES
Default
YES
Step
~
Select whether to send Activation Termination upon completion of set
point commands.
COMMUNICATION/ PROTOCOL SETUP/ IEC870-5-101/ Clock Sync’ Evt*
Range
NO, YES
Default
YES
Step
~
Select whether to generate spontaneous clock synchronization events
NOTE :
The above set values marked with * are indicated from Ver 7.06 of EVRC2A_NT.
5.2.2.3. IEC60870-5-104 Protocol - Option
EVRC2A can be programmed for communication using the IEC60870-5-104 through
communication port4.
Move to
“PRIMARY, ALTERNATE or EDITBANK SETTING
/
RELAY SETUP /
COMMUNICATION / PROTOCOL SETUP / IEC60870-5-104”
to select setting for IEC60870-
5-104 Protocol.
COMMUNICATION/ PROTOCOL SETUP/ IEC60870-5-104/ Function
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Select whether to use IEC60870-5-104 protocol or not.
COMMUNICATION/ PROTOCOL SETUP/ IEC60870-5-104/ ASDU Addr
Range
0~65535
Default
1
Step
1
Select the Application Service Data Unit Address.
[IEC60870-5-104]
>
Function: DISABLE
>ASDU Addr: 1
>
Cyclic Period: 60
[IEC60870-5-104]
>Function: DISABLE
>
ASDU Addr: 1
>
Cyclic Period: 60
[IEC60870-5-101]
>
CMD Termination:YES
>
CSE Termination:YES
>Clock Sync’ Evt:YES
[IEC60870-5-101]
>
CMD Termination:YES
>CSE Termination:YES
>
Clock Sync’ Evt:YES