COMMUNICATION/ PROTOCOL SETUP/ IEC870-5-101/ COT Size*
Range
1 ~ 2
Default
1
Step
1
Enter the size of cause of transmission.
COMMUNICATION/ PROTOCOL SETUP/ IEC870-5-101/ IOA Size*
Range
1 ~ 3
Default
2
Step
1
Enter the size of information object address.
COMMUNICATION/ PROTOCOL SETUP/ IEC870-5-101/ One Ch Response*
Range
NO, YES
Default
NO
Step
~
This allows to send one character response instead of a fixed length
NACK when no response data available.
COMMUNICATION/ PROTOCOL SETUP/ IEC870-5-101/ Fram Repet’ TO*
Range
0(OFF), 1~255sec
Default
30
Step
1 sec
Enter the time out for repetition of frames(or incremental application
layer timeout).
COMMUNICATION/ PROTOCOL SETUP/ IEC870-5-101 / Select Timeout*
Range
0(OFF), 1~255
Default
5
Step
1
Enter the period after a previously received select will timeout.
COMMUNICATION/ PROTOCOL SETUP/ IEC870-5-101/ CMD Termination*
Range
NO, YES
Default
YES
Step
~
Select whether to send Activation Termination upon completion of
commands other than set point commands.
[IEC60870-5-101]
>
Select Timeout: 5
>CMD Termination:YES
>
CSE Termination:YES
[IEC60870-5-101]
>Select Timeout: 5
>
CMD Termination:YES
>
CSE Termination:YES
[IEC60870-5-101]
>
One Ch Response: NO
>Frame Repet’ TO: 30
>
Select Timeout: 5
[IEC60870-5-101]
>One Ch Response: NO
>
Frame Repet’ TO: 30
>
Select Timeout: 5
[IEC60870-5-101]
>
COT Size : 1
>IOA Size : 2
>
One Ch Response: NO
[IEC60870-5-101]
>COT Size : 1
>
IOA Size : 2
>
One Ch Response: NO
Summary of Contents for EVRC2A-N6-NT