RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
45
EN
HANCED
TEC
HNOLOGY
COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / D/L Confirm
Range
NO, YES, SOME
Default
SOME
Step
~
Choose whether Data Link Confirm is used or not.
NO :
Data Link Confirm is not used.
YES :
Data Link Confirm is used.
SOME :
Data Link Confirm is used in case of Multi-frame.
When Data Link Confirm use-setting, it shall be set as Host setting. If
the setting is different from Host setting, the communication may be
failed due to Data Link Reset.
COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / D/L Retries
Range
0 ~ 255
Default
2
Step
1
Enter the number of retries that will be issued for a given data link
layer.
COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / D/L Timeout
Range
1 ~ 255 sec
Default
55
Step
1 sec
Set a waiting time between Data Link Frame transfer till to receive
Data Link Confirm(ACK) of Master. If there is no Data Link Confirm
receiving and Data Link retry is available, EVRC2A will send Data
Link Frame again.
COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / A/L Retries
Range
0~ 255
Default
1
Step
1
Select the number of retries that will be issued for a given application
link layer.
[DNP3.0-1]
>
D/L Retries: 2
>
D/L Timeout: 55
>A/L Retries: 1
[DNP3.0-1]
>
D/L Confirm: SOME
>
D/L Retries: 2
>D/L Timeout: 55
[DNP3.0-1]
>
D/L Confirm: SOME
>D/L Retries: 2
>
D/L Timeout: 55
[DNP3.0-1]
>D/L Confirm: SOME
>
D/L Retries: 2
>
D/L Timeout: 55