PRIMARY SETTING / SYSTEM SETUP / LOOP CONTROL / NRT After LC
Range
0.00 ~ 600.00 sec
Default
10.00
Step
0.01 sec
Non Reclose Time After LC Action :
Setting values are used in
MID, TIE.
This timer prevents from Reclosing when recloser operates due to a
fault after Loop control.
After “LL Regain T” and changed Settings, while backward
distributing line operating, if a fault occurs and MID trips within a set
time, MID reclose. MID trips once and lockouts. If a fault occurs and
MID trips after a set time, reclosing is executed.
After “LL Regain T”, when a fault occurs and TIE trips within a set
time, TIE also, trips once and lockout. If a fault occurs and TIE trips
after a set time, reclosing is executed.
[LOOP CONTROL]
>
LL Regain T: 10.00
>
DL Reset T: 5.00
>NRT After LC: 10.00