7.5. Negative Sequence (Fast/Delay) Time Overcurrent (46)
The EVRC2A has two negative sequence time overcurrent elements. The negative sequence
element measures the amount of unbalance current in the system. The negative sequence
overcurrent element can also be used to detect phase to ground and two phase ground faults. The
negative sequence time overcurrent element provides a time delay versus current for tripping
using that an inverse time curve characteristic is operated to coordinate, current pickup value,
curve type, time dial, time adder, minimum response time setting, and reset type.
The negative sequence time overcurrent element is enabled in the Primary, Alternate settings and
[PROTECTION ENABLED]
on user interface panel.
Multiple time curves and time dials are available for the negative sequence time overcurrent
element to closely coordinate with other protection elements in the EVRC2A and other external
devices on the distribution system.
The Reset type can be either instantaneous or linear. The negative sequence time delay reset
mode applies to the ANSI, IEC, ESB, USER curves. The instantaneous mode is used to
coordinate with other instantaneous reset devices such as a recloser or other protective
equipment on the distribution system. In the instantaneous mode, the time overcurrent element
will reset instantaneously when the measured current level drops below the pickup setting for
one cycle.
If the recloser is closed by pressing the CLOSE button on the front panel, or by an remote
control or via SCADA, the negative sequence time overcurrent element is prevented from
tripping for a period specified by the Cold load pickup scheme.
NEG Pickup Current Setup
The following setting is used to program the NEQ pickup current.
PRIMARY SETTING / PROTECTION / PICKUP CURRENT / NEG Seq
Range
OFF, 10 ~ 1600A
Default
OFF
Step
1A
Set the pickup current of NEG Seq Time Overcurrent elements.
[PICKUP CURRENT(A)]
Ground: 250
S.E.F: OFF
>NEG Seq: OFF
Summary of Contents for EVRC2A-N6-NT