RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
208
EN
HANCED
TEC
HNOLOGY
8. MONITORING
EVRC2A has Monitoring function for following items and also has functions for user to output
Alarm signal or Trip signal.
y
DEMAND
y
SYNCHRO CHECK
y
TRIP COUNTER
y
RECLOSER WEAR
y
BATTERY TEST
y
FAULT LOCATOR
y
GAS LOW LOCK – Option
y
EXT’ TRIP & LOCK – Option
y
LIVE LOAD BLOCK – Option
8.1. Demand
8.1.1. Description
EVRC2A is programmed to monitor following items to be operated as user sets.
y
Phase Current demand value
y
Ground current demand value
y
Negative sequence current demand value
8.1.2. Related Setting Menu
1)
Function Setting
Select for system to operate when Demand elements were picked up.
PRIMARY SETTING / MONITORING / DEMAND / Function
Range
OFF, TRIP, TR&AR
Default
OFF
Step
~
OFF :
OFF Monitoring
TRIP :
Generates Trip signal
TR&AR :
Generate Trip and Alarm signal
[DEMAND]
>Function: OFF
Relays(0-8): OFF
Type: THM