RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
97
EN
HANCED
TEC
HNOLOGY
LCD Initial Screen
Recloser type that is selected in Loop control, are displayed on LCD Initial Screen.
Press “ENT” KEY to check operation status on the Initial Screen to see loop control mode.
LOOP CONTROL: [SEC] , [MID], [TIE]
Display a selected type.
VS: [DV], [LV]
Display Source side voltage of Recloser either Dead line
voltage or Live line voltage.
VL: [DV], [LV]
Display Load side voltage of Recloser either Dead line
voltage or Live line voltage.
VSDLT: [ - ], [RUN]
Displays loop control function is operating due to the dead
line voltage of Recloser’s Source side.
VLDLT: [ - ], [RUN]
Displays loop control function is operating due to the dead
line voltage of Recloser’s Load side.
AUTO RESTORE T: [ - ], [RUN]
Displays Restoring status after Loop control operation.
LOOP CONTROL KEY
Use PROGRAM KEY to use Loop control on User interface Panel.
Figure 6-4. Loop Control Ke
y
Program 1:
Enable/Disables Loop control function.
Lamp is on when Loop control function is Enabled.
SEC, MID can be selected on CLOSE status and TIE can be
selected on OPEN status.
Program 2:
Enable/Disables Auto restoration function of
SEC, MID.
Lamp is on when Auto restoration function is enabled.
Auto restoration function is, after loop control operation,
Auto Rest’ T” timer operates till timeout, and restores the
preset values.
LOOP CONTROL [TIE]
VS-[DV] VSDLT-[ - ]
VL-[DV] VLDLT-[ - ]
AUTO RESTORE T [ - ]