RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
165
EN
HANCED
TEC
HNOLOGY
The following diagram shows the phasor diagram for I
g
directional polarization in the complex
plane.
Figure 7-9. Phasor Diagram for I
g
Directional Polarization
The ground direction control in the following four settings should be enabled.
PRIMARY SETTING / PROTECTION / DIRECTION / GROUND DIRECTION / Type
Range
OFF, FOR, REV
Default
OFF
Step
~
OFF :
None direction
FOR :
Forward direction
REV :
Reverse direction
Ma
xi
m
um
To
rq
ue L
in
e
-V0
Zero
T
orq
ue L
in
e
For
w
ar
d
Re
ve
rs
e
Ig
V
0
Polarizing Referance
Voltage:
Fault Current
[GROUND DIRECTION]
>Type: OFF
M.T.A: 135
M.P.V: 0.20