RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
126
EN
HANCED
TEC
HNOLOGY
7.1.1. Lockout
The lockout state occurs under any of the following conditions :
y
After a fault of distribution systems, the RECLOSE ENABLED LED in user interface panel
is not lighted(ON).
y
When the high current lockout has occurred.
y
The recloser is manually closed and a fault occurs before the expiration of the reset time.
y
When recloser is manually opened.
y
After TRIP occurs, the fault current is not removed or the recloser’s 52a contacts do not
change status of the recloser opened.
y
The close power waiting time delay has expired.
The Lockout State is cleared when the recloser has been manually closed by local/remote control
and the reset time has expired.
The following diagram shows the typical full protection sequence containing 2F2D (two fast and
two delay) operations followed by lockout.
(1) 1st Trip - 1st TCC
(2) 1st Reclose Interval Time
(3) 2nd Trip - 2nd TCC
(4) 2nd Reclose Interval Time
(5) 3rd Trip - 3rd TCC
(6) 3rd Reclose Interval Time
(7) 4th Trip - 4th TCC
Figure 7-2. Protection sequence containing 2F2D operations followed by lockout
(1)
(2)
(3)
(4)
(5)
(6)
(7)
NORMAL
CURRENT
PICKUP
CURRENT
FAULT
CURRENT
AMP
TIME
* LOCK-OUT *