RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
270
EN
HANCED
TEC
HNOLOGY
13.13. VD Wiring Diagram
Figure 13-12. VD Wiring Diagram
y
VD(CVD(Capacitor Voltage Divider) or RVD(Resistance Voltage Divider)) measures
Voltage with using Capacitor or Resistance installed in each Bushing of Recloser.
y
VD Type and VT Type are not exchangeable.
y
Current Inputs and Voltage Inputs should be the same phase. If CT Inputs changed Phase
rotation, Voltage Inputs phase should be re-arranged.
y
Option CVD 15
㎸
, 27
㎸
, 38
㎸
Class
y
Option RVD 15
㎸
, 27
㎸
Class
Summary of Contents for EVRC2A-N6-NT