RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
100
EN
HANCED
TEC
HNOLOGY
PRIMARY SETTING / SYSTEM SETUP / LOOP CONTROL / Cng Alt- Mid
Range
OFF, ON
Default
OFF
Step
~
Change Alternate Setting at Mid Point :
Set Value is used in
MID.
Select if Primary setting is automatically changed to Alternate setting,
after set time (LL Regain T).
To use this function, Loop control (setting value) of Primary and
Alternate shall be set as the same.
OFF :
Turn off auto change.
ON :
Turn on auto change.
PRIMARY SETTING / SYSTEM SETUP / LOOP CONTROL / Cng Alt-Tie
Range
OFF, ON(VS), ON(VL), ON(BOTH)
Default
OFF
Step
~
Change Alternate Setting at Tie Point :
Set value is used in TIE.
Select if Primary setting is automatically changed to Alternate setting,
after set time (LL Regain T).
To use this function, Loop control (setting value) of Primary and
Alternate shall be set as the same.
OFF :
Turn off auto change.
ON(VS) :
Turn on Auto change by measuring VS.
ON(VL) :
Turn on Auto change by measuring VL.
ON(BOTH) :
Turn on Auto change by measuring VS or VL.
[LOOP CONTROL]
>Cng Alt-Tie: OFF
>
LC After Cl:DISABLE
>
LC After Op:DISABLE
[LOOP CONTROL]
>
VS Wire: 3PN
>
VL Wire: 1PN(A)
>Cng Alt-Mid : OFF