RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
38
EN
HANCED
TEC
HNOLOGY
3.3.2. Setting Example
Step to change Phase Pickup current of protection elements in Primary setting.
1)
Move to
“PRIMARY SETTING / PROTECTION / PICKUP CURRENT / PHASE”
.
A following screen is displayed.
PRIMARY SETTING / PROTECTION / PICKUP CURRENT / PHASE
Range
OFF, 10 ~ 1600
Default
500
Step
1A
Set the pickup current of Phase Fast/Delay Time Overcurrent Elements.
2)
As above screen, to move to Phase, use
[
▲
] [
▼
]
key and press
[ENT]
key to move into
value column.
3)
Use
[
▲
] [
▼
]
keys and
[
◀
] [
▶
]
keys to change a new value.
Press
[ENT]
key and then you can see the changed Phase value.
NOTE:
You must save all changed values at Setting Save menu.
3.3.3. Help Function
Help function displays the detail requirements for the setting.
User can check the detail requirements of a setting after selecting the setting item by pressing
[FUN]
key.
Help Message
Help Message :
Pickup current - phase (OFF,10~1600A)
Pick up current - ph
>Phase: 500
Ground: 250
S.E.F: OFF
[PICKUP CURRENT A]
>Phase: 500
Ground: 250
S.E.F: OFF