RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
112
EN
HANCED
TEC
HNOLOGY
3-Reclosers Loop Control
For three - reclosers loop control, it consists of 2 sets of SEC(Sectionalizing Recloser), 1 set of
TIE(TIEpoint Recloser). Setting is in-turn form Source side to SEC and to TIE.
In
“Table 6-4. 3-Reclosers Setting”
, the source side bushings of RC1, RC2 are installed for CB1
side. And the source side bushings of RC3 are installed for CB2 side.
Table 6-4. 3-Reclosers Setting
SETTING CB1 RC1 RC2 RC3 CB2
Type Select
- SEC TIE SEC -
VRS – S/M
-
⎯⎯
←
VS
X
⎯→
⎯
VS
-
VRS – Tie
-
X VS&VL X
-
VS Wire
- 3PN 3PN 3PN -
VL Wire
-
1PN(A) 1PN(A) 1PN(A)
-
Cng Alt-Mid
- X X X -
Cng Alt-Tie
- X
ON
X -
LC After Cl
- ENABLE X ENABLE -
LC After Op
-
- ENABLE -
-
OT Both DL
- X
10.00
X -
Auto Rest’ T
- 5.00 5.00 5.00 -
DL V Max(%)
- 50.0 50.0 50.0 -
LL V Min(%)
- 70.0 70.0 70.0 -
DL Pickup T
- 22.0 22.0 22.0 -
LL Regain T
- 5.00
10.00
5.00 -
DL Reset T
- 5.00 5.00 5.00 -
NRT After LC
- X
10.00
X -
PROGRAM 1
-
ENABLE ENABLE ENABLE
-
PROGRAM 2
- ENABLE X ENABLE -
Reclose Time
2sec-1st reclose, 5sec-2nd reclose, 15sec-3rd reclose (lockout)
“X” is not used.