RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
289
EN
HANCED
TEC
HNOLOGY
13.34. Recloser Current Transformer (CT)
Table 13-9. Current Transformer (CT)
Description
Pin
Function
CT Ratio : (1000:1/standard)
CT Resistance
<
5
Ω
A
C.T Phase C
B
C.T Phase B
C C.T
Phase
A
D C.T
Common(G)
13.35. Recloser Voltage Divider (VD)
Table 13-10. Capacitor Voltage Divider (VD)
Description
Pin
Function
EVR RECLOSER
1)
Pin R is connected to Ground.
2)
CVD Capacitance : 20
㎊
3)
For CVD Protection, MOV is connected between
Phase and Ground.
E
CVD Source Phase C
F
CVD Source Phase B
G CVD
Source
Phase
A
H
CVD Load side Phase T
J
CVD Load side Phase S
K
CVD Load side Phase R
R
Cable shield and Ground
EPR RECLOSER
1)
Pin R is connected to Ground.
2)
RVD Resistance : 10M
Ω
3)
For RVD Protection, MOV is connected between
Phase and Ground.
y
For voltage measuring, use High Impedance AC
Voltmeter(Digital Multimeter) at Output Pin.
y
Voltage Measuring Method 1
measure MOV voltage.
(measure a voltage between MOV arms)
y
Voltage Measuring Method 2
Place the capacitor(C2) in parallel with MOV. and
measure MOV voltage.
E
RVD Source Phase C
F
RVD Source Phase B
G RVD
Source
Phase
A
H
CVD Load side Phase T
J
CVD Load side Phase S
K
CVD Load side Phase R
R
Cable shield and Ground
Figure 13-34. VD Wiring Diagram