RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
26
EN
HANCED
TEC
HNOLOGY
Protection Enabled
When illuminated, all protection elements are enabled. The protection enabled condition can be
disabled by pressing the Protection Enabled push button on the front panel. The front panel LED
will illuminate on each source of all protection enabling.
NOTE :
Although all protection elements are enabled, ground protection elements and SEF
element are operated individually.
Ground Enabled
When Ground Enable LED is ON, the ground over-current elements are enabled. The enabled
Ground can be disabled by pressing the Ground Enabled push-button on the front panel.
SEF Enabled
When SEF Enable LED is on, the Sensitive Earth Fault(SEF) element is enabled. The enabled
SEF can be disabled by pressing the SEF Enabled push-button on the front panel.
Reclose Enabled
When Reclose Enable LED is on, the reclose(79) element is enabled. The enabled reclose
element can be disabled by pressing the Recloser Enabled push-button on the front panel.
Control Locked
When Control Locked LED is on, all functions in operation section and all functions in Local
control section are locked. These can be unlocked by pressing the Control Locked push-button
on the front panel.
NOTE :
Even though Control Locked function is locked, OPEN, Lamp Test, Battery Load
Test and menu control section can be normally operated.
Remote Enabled
When Remote Enabled LED is on, all remote control functions (e.g. SCADA system) are
enabled. This can be disabled by pressing the Remote Enabled push-button on the front panel.
SCADA control refers to supported communications protocol such as DNP3.0.
Alternate Enabled
When Alternate Enabled LED is on, the Alternate setting is activated.
When Alternate Enabled LED is off, the primary setting is activated.