12.5. Fault Trip Event Recorder - Option
When fault trip occurs, fault time and fault current of each phase are recorded.
MAIN MENU / EVENT RECORDER / FAULT TRIP
Ⓐ
Ⓑ
Ex>
Confirm in
“MAIN MENU / EVENT RECORDER / FAULT TRIP”.
y
To see previous value, press
[
▲
]
key.
y
To see next value, press
[
▼
]
key.
On screen
Ⓐ
use
[
◀
]
or
[
▶
]
key to see
Ⓐ, Ⓑ
screen in term.
①
Display the order of the fault trip occurrence and events from the
most recent fault to the oldest fault.
Total 512 events can be stored.
②
Display fault sequence(shot counter).
③
Display fault type.
④
Display current of each phase when fault occurs.
⑤
Display fault time.
12.5.1. Trigger Source
y
Target elements
-
A: A Phase Overcurrent Trip
-
B: B phase Overcurrent Trip
-
C: C phase Overcurrent Trip
-
G: G phase Overcurrent Trip
-
S: Sensitive Earth Overcurrent Trip
-
Q: Negative Sequence Overcurrent Trip
-
27: Under Voltage Trip
-
59: Over Voltage Trip
-
81: Under Frequency Trip
-
O: Other Trip(Demand Current Trip, Loss of Phase etc.)
y
fault current[A]: A , B, C and G phase currents, SEF current, Negative Sequence current
[
①
/
②
]
③
IS:
④
IQ:
④
⑤
10/01/01 00:00:00
[
①
/
②
]
③
IA:
④
IB:
④
IC:
④
IG:
④
⑤
10/01/01 00:00:00
[001/1] ABCG
IA: 0 IB: 0
IC: 0 IG: 0
10/01/01 00:00:00
[001/1] ABCG
IS: 0
IQ: 0
10/01/01 00:00:00