RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
108
EN
HANCED
TEC
HNOLOGY
6.8.3. Loop Control Application
5-Reclosers Loop Control
For five reclosers loop control, it consists of 2 sets of SEC(Sectionalizing Recloser), 2 sets of
MID(MIDpoint Reclosers) and 1 set of TIE(TIEpoint Recloser). Setting is in-turn form Source
side to SEC-MID-TIE.
In “
Table 6-3. 5-Reclosers Setting
”, the source side bushings of RC1, RC2, RC3 are installed for
CB1 side. And the source side bushings of RC4, RC5 are installed for CB2 side.
Table 6-3. 5-Reclosers Setting
SETTING CB1 RC1 RC2 RC3 RC4 RC5 CB2
Type Select
- SEC
MID
TIE
MID
SEC -
VRS – S/M
-
⎯⎯
←
VS
⎯⎯
←
VS
X
⎯→
⎯
VS
⎯→
⎯
VS
-
VRS – Tie
- X X
VS&VL
X X -
VS Wire
- 3PN
3PN
3PN 3PN 3PN -
VL Wire
-
1PN(A) 1PN(A) 1PN(A) 1PN(A) 1PN(A)
-
Cng Alt-Mid
- X ON X ON X -
Cng Alt-Tie
- X X
ON
X X -
LC After Cl
- ENABLE
ENABLE
X ENABLE
ENABLE -
LC After Op
- - X
ENABLE
X - -
OT Both DL
- X X
10.00
X X -
Auto Rest’ T
- 5.00 5.00 5.00 5.00 5.00 -
DL V Max(%)
- 50.0 50.0 50.0 50.0 50.0 -
LL V Min(%)
- 70.0 70.0 70.0 70.0 70.0 -
DL Pickup T
- 22.0 22.0 22.0 22.0 22.0 -
LL Regain T
- 5.00 10.00 15.00 10.00 5.00 -
DL Reset T
- 5.00 5.00 5.00 5.00 5.00 -
NRT After LC
- X 10.00
10.00
10.00 X -
PROGRAM 1
- ENABLE
ENABLE
ENABLE
ENABLE
ENABLE -
PROGRAM 2
- ENABLE
ENABLE
X ENABLE
ENABLE -
Reclose Time
2sec-1st reclose, 5sec-2nd reclose, 15sec-3rd reclose (lockout)
“X” is not used.