RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
71
EN
HANCED
TEC
HNOLOGY
5.2.5. EVENT&ETC
Move to
“PRIMARY, ALTERNATE or EDITBANK SETTING
/ RELAY SETUP /
COMMUNICATION / EVENT&ETC”
.
COMMUNICATION/ EVENT&ETC / AI Evt Method
Range
OFF,TH,DB,BOTH
Default
OFF
Step
~
Select the Analog Event Type. This setting value is applied only to the
AI point with vitalized “Event Active” in DNP point map.
OFF :
AI Point Event doesn’t occur.
TH :
Event occurs when the AI Point data is over or less than
Threshold value.
DB :
Event occurs when the AI data change value is over the Deadband
value.
BOTH :
TH and DB are both used.
Use EVRC2A interface program to set “Event Active” enable or disable
of AI point and the Threshold value and Deadband value.
COMMUNICATION/ EVENT&ETC / SKIP at Fault
Range
NO,YES
Default
YES
Step
~
Determine whether Threshold and Deadband AI event is generated
during Fault pickup.
COMMUNICATION/ EVENT&ETC / Fault ‘I’ Evt
Range
NO,YES
Default
YES
Step
~
NO :
No Fault current event generated.
YES :
Fault current event is generated at every fault sequence.
COMMUNICATION/ EVENT&ETC / BI Queue Size
Range
32,64,128,256
Default
256
Step
~
Set the Binary Queue Size.
[EVENT&ETC]
>
BI Queue Size: 256
>
BI Evt Mode: ALL
>
AI Queue Size: 256
[EVENT&ETC]
>
AI Evt Method: OFF
>
SKIP at Fault: YES
> Fault ‘I’ Evt: YES
[EVENT&ETC]
>
AI Evt Method: OFF
> SKIP at Fault: YES
>
Fault ‘I’ Evt: YES
[EVENT&ETC]
> AI Evt Method: OFF
>
SKIP at Fault: YES
>
Fault ‘I’ Evt: YES