PRIMARY SETTING / PROTECTION / H/C LOCKOUT-NEQ / Pickup(A)
Range
10 ~ 20000 A
Default
8000
Step
1A
Set the pickup current of Negative Seq. High Current Lockout Element.
This value is the minimum operating current of Negative Seq. High
Current Lockout Element.
PRIMARY SETTING / PROTECTION / H/C LOCKOUT-NEQ / Time Delay
Range
0.00 ~ 10.00 sec
Default
0.00
Step
0.01 sec
The Time delay of phase high current trip setting programs a definite
time delay for the phase high current trip. If set to zero, phase high
current trip operates instantaneously.
PRIMARY SETTING / PROTECTION / H/C LOCKOUT-NEQ / Active Trip
Range
OFF, 1 ~ 5
Default
OFF
Step
1
If Active Trip = OFF,
the feature is not operate.
If Active Trip = 2,
then phase high current trip is enabled for the
second trip operation and every following trip operation.
[ H/C LOCKOUT-NEQ ]
Pickup(A): 8000
Time Delay: 0.00
>Active Trip: OFF
[ H/C LOCKOUT-NEQ ]
Relays(0-8): OFF
Pickup(A): 8000
>Time Delay: 0.00
[ H/C LOCKOUT-NEQ ]
Function: OFF
Relays(0-8): OFF
>Pickup(A): 8000