ENCLOSURE MOUNTING

To assist installation
a. Remove endplates for (i) drilling, (ii) for fitting  

enclosure to trunking.

b. Remove Pan Assembly by slackening Neutral Busbar  

Connection ‘N1’ and the 2 pan fixing screws.

c. Fix enclosure to wall

N.B. Endplate fixing screws are of a special type provided to  
ensure the endplates are electrically bonded to the enclosure.  
Do not replace with screws of another type. After refitting  Pan 
Assembly ensure Neutral link is connected to 

‘N1’ and all  

fixing screws are tight.

RECOMMENDED TORQUE 2.4Nm.

NOTE

To ease fitting of incoming cable the Neutral Terminal  
is removable.
1. Remove Pan assembly.
2.

Remove ‘N’ assembly by slackening ‘N’ assembly  
fixing screw(s) and pull in direction of arrow.

Earth Terminal
tighten to 6.8Nm

Pan Fixing   
Screw s

Cover  
Fixing   
Screw s

‘N’ Assembly

‘N’  Assembly  
Fixing Screw s

Pan   
Assembly

Incoming Device
tighten to 2.4Nm

IMPORTANT NOTES

1. This product should be installed,  commissioned  and maintained  by or under the supervision of a competent  electrician  

in accordance w ith current electrical engineering  Codes of Practice, Regulations  for the Electrical  equipment  of  
Buildings  (BS7671), CDM2007  - Construction  (Design and Management)  Regulations  2007, HSG150  - Health  and  
Safety in Construction, Statutory requirements and any Specific instruction issued by the Company.

2. After completing  the installation  and testing of this product it is essential that this leaflet is draw n to the attention  of  

the person responsible for its future operation and maintenance, and is at all times available for ready reference.

3. These notes assume throughout that the product is disconnected from the supply. It is essential that this is done

before any w ork is carried out.

Earth/Neutral  
terminal screws,  
tighten to 2.5Nm

MEMSHIELD 3 TYPE A SPN DISTRIBUTIONBOARD

Instruction leaflet LT1181 (01/21)

These Distribution Boards are
designed only for

use with

MCB’s and RCBO’s as listed in the
current Memshield 3 catalogue.
Failure to comply w ill result in
invalid w arranty and certification.

Blanking   
Module