background image

FITTING EMBL2

For extra security  

fit padlock

List No. PD2

FITTING DOOR LOCK EMDL & EMPL

M6 KEY HOLE FIXINGS

10

130

100

OVERALL DIMENSIONS

A

37.6

161

254

B

All dimensions in mm

A

B

EAM4

238

163

EAMMP65

238

163

EAM7

292

217

EAM10

346

271

EAM13

440

365

EAM9M/MB

440

365

EAM16

454

379

EAM12M/MB

454

379

EAMSL66M/MB

454

379

EAMSL93M/MB

454

379

=

=

Remove   

Plastic  Knob

Insert Lock into hole tighten  back nut

Warning -
Intellectual Property Rights

Eaton wishes to make it clear that it owns intellectual property rights in the
product which it manufactures (whether or not listed in this leaflet) and that
it will take legal action against any party found to be manufacturing, using,
or selling any article which infringesthe

company’s intellectual property. All

marks in this document identified with an R symbol or a TMsymbol adjacent
to the mark are trademarks of Eaton.

2019 Eaton Electric Limited.  

All rightsreserved.

www.eaton.com/recycling

The use to which this product is put and its place of installation is outside our  
control. Particular care should therefore be taken tofollow the instructions given  
here and to ensure their continued availability in conjunction with the use of the  
product.
No responsibility can be accepted by us if these instructions are disregarded.  
Further copies of these instructions and information concerning the installation  
and proper use of thisproduct can be obtained by contacting the:

Technical Services Department
Eaton Electric Limited, Middleton, Manchester, M24 1GQ. UK
Tel: +44(0)8700 545 333,
email: [email protected]

Suitable  for Indoor,  Stationary applications
Mechanical  Protection  : IK06   
IP  Rating  : IP3X
EMC  Classification : B  
Pollution  Degree : 3  
Construction Type : Fixed   
Frequency (fn) : 50Hz

MCB  (2A 

– 50A) = Rating  as marked,  (63A) = 55A Inc. Subject to applicable  RDF  - per table 101, IEC/EN61439-3

INTERFACE CHARACTERISTICS

Type A DBO  to IEC/EN61439-3

Rated  Voltage / Rated Operational  voltage (Un  / Ue) : 240V a.c.  
Rated  Impulse  Withstand Voltage (Uimp)  : 4kV
Rated  Insulation  Voltage (Ui)  : 415V
Rated  Conditional  Short Circuit Current  (Icc) : 15kA
Rated  Current of the Assembly (InA) : See DB  Rating  label (65A - 125A)  
Rated  Diversity Factor(s) RDF  : 0.7
Rated  Current of each Circuit  (Inc) :

RCCB  (100A) = 90A Inc.
RCBO  (6A-45A) = Rating  as marked 

– subject to applicable RDF

Reviews: